Small Generators 40–50 kVA

Small Generators 40–50 kVA

Bobcat's small generators, powered by the robust Hyundai D24 engine and premium components, deliver unmatched power in a compact package. With reduced noise levels, easy portability with the optional running gear, as well as optional liquid heat for extended longevity, they're perfect for rental fleets and various applications. Choose Bobcat generators for reliability and convenience.

Specifications

Compare

Key Specifications

Stand by Power
44 kVA
51.25 kVA
Prime Power
40 kVA
50 kVA
Engine
HDI 
HDI 
Alternator
Stamford 
Stamford 
Package Size – L x H x W
2207 x 1578 x 965 mm
2560 x 1576 x 970 mm
Weight (Dry)
1217 kg
1228 kg

Key Specifications

Stand by Power
44 kVA
51.25 kVA
Prime Power
40 kVA
50 kVA
Engine
HDI 
HDI 
Alternator
Stamford 
Stamford 
Package Size – L x H x W
2207 x 1578 x 965 mm
2560 x 1576 x 970 mm
Weight (Dry)
1217 kg
1228 kg

Ratings

Frequency
50.00 Hz
50.00 Hz
Prime rating power (kW)
32.00 kW
40.00 kW
Prime rating power (kVA)
40.0 
50.0 
Stand by power (kW)
35.20 kW
41.00 kW
Stand by power (kVA)
44.0 
51.25 
Alternator
400/230V 

Dimensions

Length
2207.00 mm
2560.00 mm
Width
965.00 mm
970.00 mm
Height
1578.00 mm
1576.00 mm
Lenght - OPT
2297.00 mm
2205.00 mm
Width - OPT
1055.00 mm
965.00 mm
Height - OPT
1747.00 mm
1740.00 mm

Engine

Manufacturer
HDI 
HDI 
Model
D24 
D24 
Configuration
4 Cycle; In-line; 4 Cylinder Diesel 
4 Cycle; In-line; 4 Cylinder Diesel 
Aspiration
Turbocharged and Intercooled 
Turbocharged and Intercooled 
Prime Net engine power output
37.3 kWm 
43 kWm 
Stand by Net engine power output
41 kWm 
50.1 kWm 
Bore
90.00 mm
90.00 mm
Stroke
94.00 mm
94.00 mm
Rated speed
1500.00 RPM
1500.0 
Compression ratio
18:01 
19.0:1 
Lube oil capacity
8.70 L
8.70 L
Governor type
ECU 
ECU 
Starting voltage
12 Volts DC 
12 Volts DC 
Speed regulation
+/- 0.25% 
+/- 0.25% 
Emission Level Compliance
EU Stage V 
EU Stage V 

Alternator

Alternator Manufacturer
Stamford 
Stamford 
Alternator Model
S1L2N1 
S1L2R1 
Rating continuous ( 50 Hz - kVA)
41.0 
50.0 
Voltage regulation
+/- 1% 
+/- 1% 
Excitation system STD/OPT
Aux Winding-AS540 
Aux Winding-AS540 
Impregnation
Heavy Duty Impregnation 
Heavy Duty Impregnation 
IP rating
IP23 
IP23 

Fuel Tank

Standard tank capacity
176.00 L
176.00 L
Standard tank autonomy @ 75 % load - Prime
20 hours 
19 
Extended tank capacity
386.00 L
386.00 L
Extended tank autonomy @ 75 % load - Prime
43 hours 
42 

Fuel Consumption

Prime 0%
1.60 L/h
1.60 L/h
Prime 50%
5.10 L/h
6.60 L/h
Prime 75%
7.20 L/h
9.20 L/h
Prime 100%
9.30 L/h
11.50 L/h

Electrical

Battery type
1x12V 
1x12V 
Battery Capacity
72.0 
72.0 
Battery Cold Cranking
680.00 A
680.00 A
Main circuit breaker - Brand
Schneider 
Schneider 
Main circuit breaker - Type
Manual 4P 
Manual 4P 
Main circuit breaker - Amps
100.0 
100.0 

Control Panel

Brand
COMAP 
COMAP 
Reference
MRS16 
MRS16 

Cooling

Fan load
1.4 
2.5 
Coolant capacity (with radiator)
10.20 L
10.20 L
Limited Ambient Temperature
42.0 
42.0 

Weights

Unit dry weight - Standard fuel tank
1220.00 kg
1231.00 kg
Unit dry weight - Extended fuel tank
1217.00 kg
1228.00 kg
Unit wet weight - Standard fuel tank
1354.00 kg
1365.00 kg
Unit wet weight - Extended fuel tank
1705.00 kg
1716.00 kg

Noise

Measured LWA
90.0 
90.0 
Average Noise level @ 1m @ 75 % load
71.00 dB(A)
71.00 dB(A)
Average Noise level @ 7m @ 75 % load
61.00 dB(A)
61.00 dB(A)